Some air conditioner related metrics.
Air conditioners, refrigerators and heat pumps are based on the following basic principles:
In the diagram below a compressor pumps a refrigerant through a metal pipe. At the inlet of the compressor the pressure is low. At the outlet the pressure is high. The refrigerant flows through a reduction valve which does exactly the opposite: It reduces the pressure.
Evaporator
Low pressure thus
low boiling point
Liquid evaporates
→ →
Liquid ┏━━━━━━━━━━━━━━━━━━┓ Vapor
+ vapor ┃ ┃
↑ ┃ ┃ ↓
┏┻┓ ┏┻┓
Reduction ┃↑┃ ┃ ┃ Compressor
valve ┃ ┃ ┃↓┃
┗┳┛ ┗┳┛
↑ ┃ ┃ ↓
┃ ┃
Liquid ┗━━━━━━━━━━━━━━━━━━┛ Vapor
← ←
Condenser
High pressure thus
high boiling point
Vapor condenses
At the low pressure side the the boiling point is low which evaporates the
liquid. And since evaporation requires energy the pipe in which the
evaporation takes place cools off.
At the high pressure side the boiling point is high which condenses the
gas. And since condensation releases energy the pipe in which the
condensation takes place warms up.
At the cool side the pipe runs in a zigzag through thin metal plates. A fan
blows air between the plates which cools off the air. This bit is called
the evaporator.
At the warm side there is also a zigzag through thin metal plates. Here the
air blown between the plates gets warmed up. This part is called the
condenser.
An air conditioner has the evaporator indoor and the condenser outside.
A heat pump has the condenser indoor and the evaporator outside.
Most modern air conditioners have a system of valves which make it possible
to do both.
| Poorly insulated room | 50 Watt / m³ |
| Average insulated room | 40 Watt / m³ |
| Well insulated room | 30 Watt / m³ |
The above values are required cooling power, not the electrical power
consumption. And since 1 Watt equals 1 Joule per Second, the above numbers
are the the amount of heat (thermal energy) expressed in joules that is
removed from your room every second.
The actual power consumption is much lower. The ratio between the two
determines the air conditioner efficiency:
Watts cooling power
Efficiency = ────────────────────────────────────
Watts electrical power consumption
As air conditioner technology improves, this number gets higher, which reduces your electricity bill. So you want this number to be as high as possible.
Below the theoretical maximum performance:
Indoor temperature in Kelvin
────────────────────────────────────────
Outside - Indoor temperature in Kelvin
And the same for degrees Celsius:
Indoor °C + 273.15 ──────────────────────── Outside °C - Indoor °C
Below the theoretical maximum performance as a graph for a 24°C and a 27°C
indoor temperature:

The actual efficiency is always less than this number and may be as small
as 1/10th of the theoretical maximum.
However, once your room is cool a modern air conditioner will reduce the
compressor speed and very little power is needed to keep it cool. This is
usually done by powering the compressor from a (three phase) inverter
(circuit which turns DC into AC): Reducing output frequency reduces the
compressor speed.
And the better the thermal insulation for your room, the less power your air
conditioner needs to keep it cool.
Non standard units.
Sometimes room sizes are expressed as m² instead of m³. This usually assumes a ceiling height of 2.6 m.
And yet an other
SI
vs imperial source of confusion!
A BTU or British Thermal Unit is 1055.1 Joule. And since one hour equals
3600 seconds, a BTU per hour is 1055.1 / 3600 ≈ 0.2931 Joules per Second
or Watt:
| 1 Watt | ≈ | 3.412 BTU/h |
| 1 BTU/h | ≈ | 0.2931 Watt |
A conversion table:
| BTU/h | kW |
|---|---|
| 9000 | 2.638 |
| 12000 | 3.517 |
| 15000 | 4.396 |
| 18000 | 5.275 |
| 24000 | 7.034 |
When the cooling power is expressed in BTU/h, this somehow is always a
whole multiple of 1000. My air conditioner for instance, is specified as
both 9000 BTU/h and 2.7 kW. And 3.412 x 2700 does not precisely equal
9000 (it's 9212.4). So these are rounded numbers!
Doing things this way may be more visually appealing, but doesn't provide
you with accurate information. So always look at the cooling power expressed
in kW.
Sometimes the air conditioner efficiency is expressed as BTU/h cooling
power / Watt power consumption (which equals BTU / Watt x hours). This gets
you a number that's a factor 3.412 higher than the above method, in which
case you have to divide the air conditioner efficiency value by 3.412 to get
a more realistic number.
Always make sure you're not dealing with inflated numbers!
Different ways to express how efficient an air conditioner is.
Energy Efficiency Ratio
Efficiency measured with an outside temperature of 35°C and and an indoor
temperature of 27°C at 50% humidity.
Coefficient Of Performance
This the the efficiency of a heat pump. And since most air conditioners
can also be used as a heat pump, COP is often specified as well.
Seasonal Energy Efficiency Ratio
This is more or less the average efficiency over a whole year; It's weighted
average efficiency that compensates for seasonal differences. You can think
of it as the total cooling provided in a whole year divided by the total
electricity consumption in a whole year.
In a modern air conditioner, this number tends to be a lot higher than EER.
| Outside temperature |
Weight factor |
|---|---|
| 35°C | 0.25 |
| 30°C | 0.25 |
| 25°C | 0.25 |
| 20°C | 0.25 |
The total SEER is the weighted sum of the EERs at the above values. So 1/4 of the EER at 35°C plus 1/4 of the EER at 30°C plus 1/4 of the EER at 25°C plus 1/4 of the EER at 20°C.
Some websites specify SEER in BTU/Wh instead of W/W (those inflated numbers again). Below a conversion table:
| BTU/Wh | W/W |
|---|---|
| 30 | 8.8 |
| 27 | 7.9 |
| 25 | 7.3 |
| 22 | 6.4 |
| 20 | 5.9 |
| 17 | 5.0 |
| 15 | 4.4 |
So, if somebody advertises a SEER of 20, it's probably BTU/Wh and not
W/W!
And from W/W to BTU/Wh:
| W/W | BTU/Wh |
|---|---|
| 8.5 | 29.0 |
| 6.1 | 20.8 |
| 5.6 | 19.1 |
| 5.1 | 17.4 |
| 4.6 | 15.7 |
Seasonal Coefficient Of Performance
This is more or less the average efficiency of a heat pump over a whole
year; It's weighted average efficiency that compensates for seasonal
differences.
European SEER:
| Load factor |
Outside temperature |
Weight factor |
|---|---|---|
| 100% | 35°C | 0.03 |
| 75% | 30°C | 0.31 |
| 50% | 25°C | 0.41 |
| 25% | 20°C | 0.23 |
| Efficiency class |
SEER W/W |
|
|---|---|---|
| A+++ | ≥ 8.50 | |
| A++ | 6.10 - 8.49 | |
| A+ | 5.60 - 6.09 | |
| A | 5.10 - 5.59 | |
| B | 4.60 - 5.09 | |
Energy labels may get as low as 'G', but air conditioners with a label
below 'B' are not allowed.
I have never seen any air conditioners with a label below 'A' though. Most
are 'A+' or higher.
Note: Efficiency classes may change as regulation gets more strict!
For comparison below some sound levels.
| dB | Noise |
|---|---|
| 10 | Normal breathing, A pin dropping |
| 20 | Rustling leaves |
| 30 | Whisper |
| 40 | A quiet residential area |
| 50 | Quiet Home, Light traffic |
| 60 | Normal conversation |
| 70 | Busy Restaurant, Shower |
Indoor units tend to be quieter than outdoor units. And keep in mind that a fan sounds less annoying than a compressor.